Product

Accutech TC10 Wireless Thermocouple Temperature

The Accutech TC10 wireless thermocouple temperature field unit provides temperature data using standard J, K, S and T-type thermocouples. Probes are available with either spring-loaded or direct insertion fitting in a variety of with probe lengths.

Accutech field units automatically report field data to a centralised Accutech base radio over distances of up to 3000ft (~1000m). Each field unit is self-contained, featuring an integrated 900MHz or 2.4GHz (license-free band), frequency hopping, spread-spectrum transceiver and antenna, and long lasting battery that offers 3+ years of maintenance-free service (up to 10 years depending on data rates and battery options). Accutech networks are highly scalable with the possibility of 100 field units per base radio and 256 base radios per installation. Accutech field units are housed within a compact and weather-resistant NEMA4 enclosure with options for a remote sensor and remote antenna on select models. Field units are available in a wide range of certifications and come with a 3-Year warranty (parts and labor).
 

Accutech TC10 Wireless Thermocouple Temperature

• Sensor Type Thermocouple Temperature
• Frequency Range 900MHz and 2.4GHz license-free bands
• Network Capacity • Max. 100 field units per base radio
                              • Max. 256 base radios per network
• Sensor Accuracy Electronics accuracy: ± 0.1 percent of full-scale reading plus 1°C (1.8 °F) for thermocouple cold-junction effect at reference conditions
• Ambient temperature effect: ± 0.01% of reading per °C (1.8 °F) ambient temperature difference from reference condition (20°C or 68°F).
• Stability: Deviation per year is less than 0.025%
• Thermocouple accuracy:
        : J-Type: the greater of +/- 1.1°C (2°F) or 0.4% of reading
        : K-Type: the greater of +/- 1.1°C (2°F) or 0.4% of reading
        : S-Type: the greater of +/- 0.6°C (1.1°F) or 0.1% of reading
        : T-Type: the greater of +/- 0.5°C (0.9°F) or 0.4% of reading
• Stability Deviation per year is less than 0.025%
• RF Characteristics 2.4GHz:
       : 2400 to 2483.5MHz ISM license-free band Frequency Hopping Spread Spectrum (FHSS) Radio
       : Data Rates: 50/100kbps (FSK Modulation), 200kbps (GFSK Modulation)
       : Typical Electrical Transmit Power: +10.6dBm
       : Typical Receive Sensitivity (0.1% BER): - 102dBm @ 50kbps, - 99dBm @ 100kbps, - 99dBm @ 200kbps
       : Typical CW Receiver Blocking Rejection: 64dB for CW @ +/- 5MHz, 74dB for CW @ +/- 30MHz
• Self-Diagnostics • Low battery notification – indicates the need to replace the battery (approximately one month advance notification).
• Contains extensive self-checking software and hardware that continuously monitors operation. Any sensor or device parameter that is out of spec is identified and reported.
• Operating Ambient: -40 to +85°C
• Thermocouple Types • J 0° to 760°C (32° to 1400°F)
: K 0° to 1260°C (32° to 2300°F)
: S 0° to 1480°C (32° to 2700°F)
: T 0° to 370°C (32° to 700°F)
• Power • Standard Accutech field units include a single C-Cell (900MHz) or D-Cell (2.4GHz) lithium battery that offers battery life up to 10 years of service, depending on data rates and battery options.
• Physical Characteristics
: Base Plate: 304 Stainless Steel
: Cover: GE Lexan®, V-0 rating and UV resistant
: Process Connection: 1/2” MNPT
• Operating Shock and Vibration: Tested per IEC 60068-2-6 (vibration) and 2-27 (shock)
• Random Vibration Characteristics: Tested to withstand 6 g’s, 15 minutes per axis from 9 – 500Hz
 

Accutech TC10 Wireless Thermocouple Temperature